ASHRAE 55
ANSI/ASHRAE Standard 55 (Thermal Environmental Conditions for Human Occupancy) is a standard that provides minimum requirements for acceptable thermal indoor environments. It establishes the ranges of indoor environmental conditions that are acceptable to achieve thermal comfort for occupants. It was first published in 1966, and since 2004 has been updated periodically by a technical committee of industry experts in ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers). The most recent version of the standard was published in 2013.
Organization of standard
The body of the standard currently consists of a forward (describing changes made in the current version), eight sections and two normative appendices:
- Purpose
- Scope
- Definitions
- General requirements
- Conditions that provide thermal comfort
- Design compliance
- Evaluation of comfort in existing buildings
- References
- Normative Appendix A: Methods for determining operative temperature
- Normative Appendix B: Computer program for calculation of PMV/PPD
After the body of the standard there are 11 informative appendices. These are not part of the standard, but provide additional information about terms and methods described within the standard, as well as a bibliography, and a description of the addenda incorporated from the previous version in the current version.[1]
Purpose
As described within the standard: "The purpose of the standard is to specify the combinations of indoor thermal environmental factors and personal factors that will produce thermal environmental conditions acceptable to a majority of the occupants within the space".[1]
Scope
The standard addresses the four primary environmental factors (temperature, thermal radiation, humidity, and air speed) and two personal factors (activity and clothing) that affect thermal comfort. It is applicable for healthy adults at atmospheric pressures in altitudes up to (or equivalent to) 3,000 m (9,800 ft), and for indoor spaces designed for occupancy of at least 15 minutes.[1]
Definitions
Adaptive model
Adaptive model is a model that relates indoor design temperatures or acceptable temperature ranges to outdoor meteorological or climatological parameters.[1]
Thermal comfort
Thermal comfort is the condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation.[1]
Occupant-controlled naturally conditioned spaces
A occupant-controlled naturally conditioned space is where the thermal conditions of the space are primarily regulated by occupant-controlled openings.[1]
Predicted mean vote (PMV)
Predicted mean vote is an index that predicts the mean value of the thermal sensation votes (self-reported perceptions) of a large group of persons on a sensation scale expressed from -3 to +3 corresponding to the categories "cold," "cool," "slightly cool," "neutral," "slight warm," "warm," and "hot."[1]
Comfort zone
Comfort zone refers to the combinations of air temperature, mean radiant temperature (tr), and humidity that are predicted to be an acceptable thermal environment at particular values of air speed, metabolic rate, and clothing insulation (Icl)[1]
Clothing insulation (Icl)
Clothing insulation is the resistance to sensible heat transfer provided by a clothing ensemble (expressed in units of clo, which is a unit to quantify the insulation provided by garments and clothing ensembles. 1 clo = 0.155 m² °C/W (0.88 ft²·h·°F/Btu))[1]
Metabolic rate (met)
Metabolic rate is the rate of transformation of chemical energy into heat and mechanical work by metabolic activities of an individual, per unit of skin surface are (expressed in units of met) equal to 58.2 W/m² (18.4 Btu/h·ft²), which is the energy produced per unit skin surface are of an average person seated at rest.
Exceedance hours
Exceedance hour is the number of occupied hours within a defined time period in which the environmental conditions in an occupied space are outside the comfort zone.[1]
Methods to evaluate thermal comfort
Graphic comfort zone method
The graphic method utilizes an overlay on a psychrometric chart to indicate the operative temperatures and humidity at which thermal comfort is achieved in the winter (1.0 clo) and summer (0.5 clo). It is based on the Predicted Mean Vote (PMV) model.[2] The graphic comfort zone model is limited in applicability to conditions when the metabolic rate of occupants is 1.0-1.3 met and the humidity ratio is below 0.012 kg H2O/kg dry air (0.012 lb H2O/lb dry air). If these requirements are met and the environmental conditions inside the building fall within the indicated ranges, then compliance is achieved.[1]
Analytical comfort zone method
For humidity ratios above 0.012 kg H2O/kg dry air (0.012 lb H2O/lb dry air), or for metabolic rates up to 2.0 met, the analytical model must be used to determine thermal comfort sensation. Also based on the PMV model, this method uses tools such as the ASHRAE Thermal Comfort Tool or the online CBE Thermal Comfort Tool[3] to evaluate thermal comfort. Users provide operative temperature (or air temperature and mean radiant temperature), air speed, humidity, metabolic rate, and clothing insulation value, and the tool evaluates predicted thermal sensation on a scale from -3 (cold) to +3 (hot). Compliance is achieved if the conditions provide thermal neutrality, measured as falling between -0.5 and +0.5 on the PMV scale.[1]
Elevated air speed
The section sets provisions for increasing the upper air temperature limit at elevated air speeds above 0.20 m/s (39 ft/min). The methodology is based on the SET (Standard Effective Temperature) model, which provides a way to assign an effective temperature (at a standard metabolic rate, and clothing insulation values) to compare thermal sensations experienced at a range of thermal conditions.[4] The upper limit of air speed is based on whether occupants have local control or not. To evaluate compliance, the ASHRAE Thermal Comfort Tool may be used, or a computer model validated against the code provided in Informative Appendix G of the standard.[1]
Local thermal discomfort
Radiant temperature asymmetry between ceiling and floor, and air and walls must be limited to reduce discomfort. To reduce draft risk at temperatures below 22.5 °C (72.5 °F), air speed due to the HVAC system must be 0.15 m/s (30 ft/min) or below. The vertical air temperature difference between ankle and head is limited to 3 °C (5.4 °F) for seated occupants and 4 °C (7.2 °F) for standing occupants.[5] If occupants' feet will be in contact with the floor, the temperature must be 19–29 °C (66–84 °F).[1]
Temperature variations with time
When occupants do not have control over the cyclical variation or drifts in indoor environmental conditions, the conditions within this section must be met. Operative temperatures may not fluctuate more than 1.1 °C (2.0 °F) within 15 minutes, nor change more than 2.2 °C (4.0 °F) within 1 hour.[1]
Acceptable thermal conditions in occupant-controlled naturally conditioned spaces
This method, also known as the adaptive comfort model, is applicable in buildings without mechanical cooling (and no operating heating system) where occupants’ met rates are 1.0-1.3 met and their clothing levels are 0.5-1.0 clo. For this model the standard provides a graph of acceptable indoor temperature limits at prevailing mean outdoor temperatures (a mean of the daily mean outdoor temperatures of the previous 7–30 days). An accompanying table lists provisions for higher operative temperatures at air speeds above 0.3 m/s (59 ft/min) and up to 1.2 m/s (240 ft/min). The graph is valid for prevailing mean temperatures between 10–33.5 °C (50.0–92.3 °F). It provides 80% and 90% acceptability ranges, indicating the percentage of occupants expected to be comfortable at the indicated indoor and prevailing mean outdoor temperatures.[1]
Demonstrating design compliance
This section of the standard is applicable for the design of buildings. All of the building systems must be designed to maintain the occupied spaces at the indoor conditions specified by one of the described evaluation methods at design conditions. The systems must be able to maintain these conditions within the expected range of indoor and outdoor operating conditions.[1]
To demonstrate compliance the following must be documented, where applicable. Sample documentation is provided in Informative Appendix J.[1]
- Method of compliance (e.g. Graphic Comfort Zone Method)
- Design operative temperature and humidity, heating and cooling design outdoor conditions, total indoor loads, and design exceedance hours
- Assumed values for environmental factors (operative temperature, humidity, and average air speed) and personal factors (clothing insulation and metabolic rate) for heating and cooling design conditions; spaces where personal factors are outside the specified limits should be indicated as not within the standard’s scope
- A description of how local thermal discomfort will be addressed, including calculation methods, inputs and results
- System equipment capacities for each space demonstrating that thermal loads will be met under heating and cooling design conditions
- Where occupant-controlled elevated air speed is provided, a description of control type
- Air speed, radiant temperature asymmetry, vertical radiant temperature asymmetry, surface temperatures, and temperature variations in time must be calculated per engineering industry standards (e.g. Chapter 57 of the ASHRAE Handbook-HVAC Applications)
Evaluation of comfort in existing buildings
Although the ANSI/ASHRAE Standard 55 does not require the evaluation of comfort in existing building, this part of the standard offers a guideline of performing an evaluation when one is required from other codes or standard. Generally, the evaluation of comfort in existing buildings can be performed from two perspectives: from occupant satisfaction survey and physical environmental measurements.[1]
Measurement methods
Occupant Survey
Indoor thermal comfort can be determined from the responses of the occupant survey. The survey shall be distributed to the entire occupancy or representative part of the occupancy. The standard suggests that if the surveys were distributed to more than 45 occupants, the response rate must exceed 35%. If that number is between 20 and 45, the minimum number of responses is 15. When the number is under 20, at least 16 must reply for the survey to make the survey representative.[1]
For satisfaction surveys, the thermal satisfaction scale shall end with choices: "very satisfied" and "very dissatisfied", and, also, the occupants should be allowed to explain their dissatisfaction by answering an open-ended question. As for point-in-time surveys, the survey should be solicited during the time of occupancy, and the satisfaction scale ought to be continuous. There should be at least seven points on the scale ending with "very acceptable" and "very unacceptable." The standard also specifies that when asking thermal sensation questions, the scale should be "cold, cool, slightly cool, neutral, slightly warm, warm, and hot." [1]
Physical measurements
For mechanically conditioned spaces, the PMV-based comfort zone has to be determined, which includes measuring and recording the metabolic activity and clothing insulation. The comfort zone boundaries must be adjusted to the air movements, and the zone conditions should be adjusted to avoid local thermal discomfort. For occupant-controlled naturally conditioned space, the adaptive model shall be used to determine the thermal comfort boundaries. For such spaces, the indoor and outdoor air temperature and mean radiant temperature and the air speed need to be measured.[1]
ANSI/ASHRAE Standard 55 provides guideline on the position, time, and equipment accuracy of the physical measurement. The measurement locations should be where the occupants are expected to spend time in. If there are multiple such locations, the measurement can be performed at a representative location.[1] In cases that the optimal representative location cannot be found, the standard suggests specific locations in the space.[1]
For seating occupants, the air temperature and air speed measurements shall be taken at heights of 0.1, 0.6, and 1.1 m (4, 24, and 43 in.), and operative temperature and PMV shall be measured at 0.6 m (24 in.). The heights need to be adjusted for standing persons. Local discomfort caused by radiant temperature asymmetry shall be measured at occupants’ locations, with the sensors oriented to catch the maximum surface temperature differences.[1]
The standard suggests that the time of measurements should last two or more hours long, and it should also be a representative time of the year for this specific building. Measuring time step should be no more than five minutes for air temperature, mean radiant temperature, and humidity, and no more than three minutes for the air speed.[1]
In order to achieve acceptable results, the standard also suggests the minimum equipment accuracy based the current industry standard.[1]
When extracting environmental data from the Building Administration System, one should evaluate the location, height, and time step of the sensors based on the previous suggestion.[1]
Evaluation methods
Occupant Survey
To evaluate the probability of satisfaction from satisfaction surveys, the standard suggests dividing the number of the votes falling between "just satisfied" and "very satisfied" by the total number of votes in that questions. The answers of open-ended questions from "very dissatisfied" occupants should be documented for later analysis.[1] For point-in-time surveys, the comfort evaluation shall be performed by dividing the number of votes between -1 and +3 by the total number of votes. One has to keep in mind that the results from point-in-time surveys are only effective during the time when the surveys were solicited.[1]
Physical measurements
The measured results should be evaluated against the adjusted comfort zone for the specific building. There are two cases when evaluating thermal comfort: at a specific time or over a period of time. For a mechanically conditioned space at an instance in time, the PMV and SET model shall be used to establish the comfort zone, and the local thermal discomfort shall be evaluated against the limit posed this standard as well. For occupant-controlled naturally conditioned spaces, the measured results shall be check with the comfort zone established by adaptive model.[1]
To evaluate the thermal comfort over a period of time in a mechanically conditioned space, the exceedance hours are the sum of all the hours when the absolute value of PMV is greater than 0.5. For an occupant-controlled naturally conditioned space, the exceedance hours are the sum of hours when the operative temperature falls outside of the lower and upper boundaries of the comfort zone.[1]
Appendix D: Use the metabolic rate data
Metabolic rate is the rate of transformation of chemical energy into heat and mechanical work by metabolic activities of an individual. It is defined as per unit of skin surface area which equals to 58.2 W/m² (18.4 Btu/h·ft²). This is the energy produced from a unit skin surface area of an average person seated at rest.[1]
ANSI/ASHRAE Standard 55 provides a table of metabolic rate of different continuous activities. These values are valid for an average adult with surface skin area of 1.8 m² (19.6 ft²). The standard reminds the users that they should use their own judgment to match the activities being considered to the comparable activities in the table. Except sedentary activities, metabolic rate for all other activities is likely to have range of variation. This variation is depending on the individual performing the task and his/her environment.[1]
When the duration of an activity is equal or less than one hour, one can use a time-weighted metabolic rate. As metabolic rates increase over 1.0 met, the evaporation of the sweat becomes an increasingly important factor, and the PMV method does not fully account for this factor.[1]
Appendix E: Clothing insulation
Clothing insulation refers to the heat transfer of the entire body, which includes the uncovered parts, such as hands and heads. There is a variety of means to determine the insulation provided by clothing. Accurate data from the measurement using thermal manikins is acceptable. When such measurement is no feasible, this standard provides four methods to determine the clothing insulation. It is also specified that the methods provided by this standard are no longer valid when the clothing insulation exceed 1.5 clo. And it is also not valid when occupants wear clothing that is highly impermeable to moisture transport.[1] The first method is the least accurate, according to ANSI/ASHRAE Standard 55, and the accuracy increases in order of the methods.[1]
First, one can estimate the clothing insulation from the table provided in section five. If the clothing ensemble in question reasonably matches the clothing ensemble in the table, the indicated value can be used. The second method is to add or subtract individual garment clo value to achieve the clothing ensemble in question. Section five of the ANSI/ASHRAE Standard 55 provides a table with clothing insulation of a variety of individual garments. This table can be used together with the previous one, so that one can add or subtract the clothing ensemble from the clo value of each garment. The third method is to add all the clo value of each garment to match the clothing ensemble in question.[1]
The fourth method described in ANSI/ASHRAE Standard 55 can be used to determine the clothing insulation in mechanically conditioned spaces. This method is based on the concept that when occupants choose their clothing according to their environment, the outdoor environment is more influential than the indoor one. There is a figure in the section five of the standard which predicts the representative clothing insulation of the occupants as a function of the average outdoor air temperature at 06:00 am. The function line has four segments: the average outdoor air temperature is below −5.0 °C (23.0 °F), between −5.0 °C (23.0 °F) and 5.0 °C (41.0 °F), between 5.0 °C (41.0 °F) and 26.0 °C (78.8 °F), and above 26.0 °C (78.8 °F).[1]
There is a function to determine the representative clothing insulation at each segment. One can also take into account the posture of the occupants. So far, all the clothing insulation value can be used when the occupant is standing. When occupant is sitting, one has to realize the insulation effect of the chair, and the decrease of insulation due to compression of the air in the clothing.[1]
If the occupant is moving, it also affects the insulation value of clothing. In general, body motion decreases the clothing insulation by pumping air through clothing. ANSI/ASHRAE Standard 55 realizes that this effect varies largely depending on the nature of the movements and the nature clothing, such as how tight the clothing is. Thus, it only provides an approximation of the clothing insulation value of a moving person. This approximation is an equation that relates the clothing insulation with the metabolic rate. And this equation is only valid when the metabolic rate is between 1.2 and 2.0.[1]
ANSI/ASHRAE Standard 55 also states that the thermal environment conditions desired for sleeping and resting vary largely among individuals and cannot be determined using the methods provided in this standard. Considering that a sleeping person or one in reclining posture will be provided with sufficient insulation with the bedding material, and he or she is also free to adjust, it is impossible to determine the clothing insulation effect for these occupants unless they are immobile.[1]
ASHRAE Standard 55 cautious the users that there are two form of the variability among occupants. In the first form, different individuals wear different clothing due to factors that are not related to thermal conditions, and the second form is opposite. For the first, it is not correct to use the average clothing insulation value to determine the desired thermal conditions for all occupants.[1]
History of the standard
ANSI/ASHRAE Standard 55 was first published in 1966. It was revised in 1974, 1981, 1992, 2004, 2010, and 2013. Starting in 2004, it is now updated based on ASHRAE’s standard maintenance procedures. These periodic revisions are based on publicly reviewed addenda to the previous version available on ASHRAE’s website.[6]
In 1992 the standard was updated with more extensive information on measurement protocols and an expanded definitions section.[7]
In 2004 the standard underwent significant changes with the addition of two thermal comfort models: the PMV/PPD model and the adaptive comfort model.[6]
In 2010 the standard included the following changes. It re-introduced the Standard Effective Temperature (SET) as a method to calculate the cooling effect of air movement. It also added a general satisfaction survey to section 7 intended to evaluate general thermal comfort in an occupied space, bringing the standard in line with current survey-based post-occupancy evaluation (POE) practices.[8]
In 2013 the body of the standard was rewritten in mandatory language, with informative language moved from the body of the standard to informative appendices. The applicability of the cooling effect of air movement was expanded to apply to naturally conditioned spaces. Section 7 underwent major revisions for measuring thermal comfort in existing spaces including procedures for physical measurements and survey methods, and how to evaluate and report results. The last major change concerns measuring air speed and air temperature experienced by the occupant, which now must be an average across three heights and over a period of time.[1]
See also
References
- 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 ASHRAE Standard 55 (2013). "Thermal Environmental Conditions for Human Occupancy".
- ↑ Fanger, P.O. (1970). Thermal Comfort. Copenhagen: Danish Technical Press.
- ↑ Hoyt, Tyler; Schiavon, Stefano; Piccioli, Alberto; Moon, Dustin; Steinfeld, Kyle (2013). "CBE Thermal Comfort Tool". Center for the Built Environment, University of California, Berkeley. Retrieved 24 November 2014.
- ↑ Nishi, Y; Gagge, A.P. (1977). "Effective temperature scale useful for hypo-and hyperbaric environments". Aviation, space, and environmental medicine. 48 (2): 97–107.
- ↑ "Addendum a to Standard 55-2013" (PDF). ASHRAE. Retrieved 5 December 2014.
- 1 2 ASHRAE Standard 55 (2004). "Thermal Environmental Conditions for Human Occupancy".
- ↑ ASHRAE Standard 55 (1992). "Thermal Environmental Conditions for Human Occupancy".
- ↑ ASHRAE Standard 55 (2010). "Thermal Environmental Conditions for Human Occupancy".
External links
- ANSI/ASHRAE Standard 55-2010 Standard references (Appendix H) Provides a list of references in the 2010 version of the standard, with direct links to papers where possible.
- ASHRAE Website
- CBE Thermal Comfort Tool