IEC 60309

In the foreground, a downward-angled industrial wall socket with a red cap, mounted to a wall; a red plug is inserted into it. In the background, another similar connection.
Two IEC-60309-style plugs inserted into wall-mounted sockets

IEC 60309 (formerly IEC 309 and CEE 17, also published by CENELEC as EN 60309) is an international standard from the International Electrotechnical Commission (IEC) for "plugs, socket-outlets and couplers for industrial purposes". The highest voltage allowed by the standard is 690 V DC or AC; the highest current, 125 A; and the highest frequency, 500 Hz. The temperature range is −25 °C to 40 °C.[1]

There is a range of plugs and sockets[2] of different sizes with differing numbers of pins, depending on the current supplied and number of phases accommodated. The fittings also include limited (IP44) weather-proofing, that is one reason for choosing these fittings when the connections will be used in open-air conditions; a further reason for using these (other than when the heavy-current or three-phase facilities are actually needed), is to deter potential users from connecting domestic appliances to the sockets, as 'normal' domestic plug-tops will not fit.

The cable connectors and sockets are colour-coded, according to the voltage range and frequency used; for example, common colours are yellow for 100–130 volts and 50–60 Hz, blue for 200–250 volts and 50–60 Hz, and red for 400–480 volts and 50–60 Hz. Color codes depend on the highest, phase-to-phase, voltage. In addition to the colour-coding the voltage and frequency are encoded by the keyway position. The blue fittings are often used for providing weather-proofed exterior sockets for outdoor apparatus. The yellow fittings are used to provide transformer isolated 110 V supplies for UK construction sites to reduce the risk of electric shock and this use spills over into uses of power tools outside of the construction site environment. In camping situations, the large 32 A blue fittings provide power to static caravans, whilst the smaller blue 16 A version powers touring caravans and tents. The red three-phase versions are used for three-phase portable equipment.

Standardization

IEC 60309-1 specifies general functional and safety requirements for any form of industrial high-current power connector.[3] IEC 60309-2 specifies a range of mains power connectors with circular housings, and different numbers and arrangements of pins for different applications. IEC 60309-3 dealt with connectors for use in explosive gas environments, but was withdrawn in 1998.[4]

The standardization was originally done by the CEE (Commission internationale de réglementation en vue de l'approbation de l'équipement électrique), being a European certification body that became the IECEE in 1985 (International Commission on the Rules for the Approval of Electrical Equipment) as part of the IEC. It is the same standardization body that produced the "CEE 7" series of domestic AC plugs: CEE 7/4 alias German Schuko, CEE 7/5 French, CEE 7/7 French/German hybrid plug, and later the CEE 7/16 Europlug. The industrial sockets were standardized in the 1960s in the CEE 17 series that was adopted in the UK as BS 4343 and which were later to become the IEC 60309 standard.[5]

IEC 60309-4 concerns switched socket-outlets and connector interlocks. In the United Kingdom, this standard was first adopted as BS 4343:1968 and has since been replaced by its European equivalent BS EN 60309-4.[6] In the UK these plugs are often referred to as caravan, Commando (a brand name used by MK Electric), CEE industrial, CEEform or simply CEE plugs.

Colour identification

Two power cables, each with a 3P+N+E plug at one end, and a matching socket at the other end. The upper cable has blue connectors; the lower cable has red connectors.
Cables with 3P+N+E connectors

The colour of an IEC 60309 plug or socket indicates its voltage and frequency rating. The most widespread colours are yellow (125 V), blue (250 V), and red (400 V). The black version (500 V) can often be found on ships.

Characteristic Colour Earth pin
(o'clock)
Note(s)
100–130 V Yellow 4 [note 1]
120, or 240 V Orange 12 [note 2][note 3]
200–250 V Blue 6 [note 4]
120–250 V Blue 9 [note 5]
12–24 V DC Purple 12
50–250 V DC White 3
>250 V DC White 8
277 V 60 Hz only Grey 5 [note 4][note 2]
380 V 50 Hz only Red 3 [note 5][note 6]
380–480 V Red 6 [note 5]
380–480 V Red 11 [note 7]
380–415 V Red 9 [note 4]
440 V 60 Hz only Red 3 [note 5][note 6]
480–500 V Black 7 [note 5]
500–690 V Black 5 [note 5]
100–300 Hz Green 10 [note 8][note 6]
300–500 Hz Green 2 [note 9][note 6]
Any of the above Grey 12 [note 10]
None of the above Grey 1 [note 11]
Notes
  1. Single phase voltage or three phase line voltage (phase-phase) including supplies from an isolating transformer.
  2. 1 2 For countries only where Series II current ratings (20, 30, 60, 100 amps) are used.
  3. North American 120/240 V single-phase system. Four pin (2P+N+E) connector only.
  4. 1 2 3 Single phase.
  5. 1 2 3 4 5 6 Three phase line voltage (phase-phase).
  6. 1 2 3 4 Only available in 16 and 32 Amp sizes.
  7. Three phase line voltage (phase-phase) at 60 Hz only.
  8. Greater than 50 volts three phase line voltage (phase-phase). Not available in single phase version.
  9. Greater than 50 volts single phase or three phase line voltage (phase-phase).
  10. Single and 3 phase (3P+E only) supplied from an isolating transformer (except for yellow plug supplies).
  11. Most frequently used for low voltage supplies that do not fall into any of the specified ranges.

Keying

32 A 400 V 3P+N+E 6h (180°) plug
Mated 16 A plug and wall-mounted socket

IEC 60309-2 connectors are produced in many variants, designed so that a plug of one type can only be inserted into a socket of the same type. Different current ratings (such as 16 A, 32 A, 63 A and 125 A) are distinguished by different diameters of the circular housing.

Different voltage and frequency combinations are distinguished by the location of the ground pin (or a plastic projection called the minor keyway, for connectors with no ground pin), as shown in the following table. The ground pin can be in one of twelve locations spaced at 30° intervals around the circle on which all the pins lie. The various positions are referenced from the view of the open side of a socket; the 6 o'clock (180°) position is at the same angle as the major keyway, and is oriented downwards. The major keyway is a projection on the plug casing that aligns with a notch on the socket. The ground pin has a larger diameter than the other pins, preventing the wrong type of plug being inserted in a socket.

Ground pin
location
Pin configuration (P: pole, N: neutral, E: earth or ground)
P+N+E, 2P+E 3P+E 3P+N+E
60° / 2h >50 V 300–500 Hz green housing >50 V 300–500 Hz green housing >50 V 300–500 Hz green housing
90° / 3h 50–250 V DC 380 V 50 Hz
440 V 60 Hz red housing
220/380 V 50 Hz
250/440 V 60 Hz
red housing
120° / 4h 100–130 V AC yellow housing 100–130 V AC yellow housing 57–75/100–130 V AC yellow housing
150° / 5h 277 V 60 Hz grey housing 600–690 V AC black housing 347–400/600–690 V AC black housing
180° / 6h 200–250 V AC blue housing 380–415 V AC red housing 200–240/346–415 V AC red housing
210° / 7h 480–500 V AC black housing 480–500 V AC black housing 277–288/480–500 V AC black housing
240° / 8h 250 V DC
270° / 9h 380–415 V AC red housing 200–250 V AC blue housing 120–144/208–250 V AC blue housing
300° / 10h >50 V, 100–300 Hz green housing
330° / 11h 440–460 V 60 Hz red housing 250–265/440—460 V 60 Hz, red housing
360° / 12h 125/250 V
single phase (2P+N+E)
orange housing

Pilot contact

63 A plug with pilot contact

Connectors rated at 63 A and 125 A may optionally be equipped with a 6 mm pilot contact. This smaller pin in the centre of the connector is designed to 'make' after all the other pins when connecting a plug and socket, and to 'break' first when disconnecting. It is used to control the supply of power at the source. This is useful as disconnecting under load will cause arcing which may cause damage to both the plug and socket, and risk injury to the user.

The pilot pin is located in the centre of main contact circle on 4- and 5-pin connectors. On 3-pin (2P+E) connectors, it is located on the contact circle opposite the ground pin. (The other connectors are located 105° on either side of the earth pin, rather than 120° as in the smaller variants, to make room for the pilot pin.)

Common plugs

400 V phase swap plug

The most common plug types are:

The colour of the casing refers to the highest line to line voltage of the electric power distribution:

Red 3P+N+E, 6h

The red 3P+N+E, 6h (180°) plug allows to connection to the widespread 400 V three phase power network. The most common ratings are 16 A, 32 A and 63 A, with 125 A and 200 A less common. Construction sites in central Europe have most of their higher power cabling setup with this three phase socket type as the single phase to neutral voltage of 230 V is available for other devices. So called power splitters with this connector as a 3 phase inlet and 3 groups of single phase outputs with individual circuit breakers are generally used to achieve this, and allow load balancing across the phases, important on generator supplies. Similar configurations are used for outdoor exhibitions, festivals and large events.

The five pins are positioned in a circle with the ground connector E to be thicker and longer than the phase and neutral pins. When looking at the socket, the phase sequence should be L1, L2, L3. Since some wiring may be reversed, which could make motors turn backward, many machines on construction sites feature a phase swap plug that allows to swap two pins and so reverse the phase sequence.

Three-phase electric motors do not need the neutral wire to function, so that there is also a Red four pin variant (3 phases and earth) of the IEC 60309 plugs for three phase power. The two styles are not intermatable, to prevent a potential floating neutral.

Blue P+N+E, 6h

16 A 230 V P+N+E 6h plug

The blue P+N+E, 6h (180°) plug is a single phase connector. In particular the smallest (16 A) variant has become especially common in camping vehicles and sockets found in caravan parks and marinas throughout Europe. The so-called 'Caravan Mains Socket' has almost universally replaced a wide variety of other national 230 V domestic plugs since it is pan-European and inherently safe to standard IP44. On larger temporary buildings, particularly with electric heating the larger 32 A is more common.

Not all installations distinguish the live (phase) and neutral conductors, and reverse wired sockets are quite common, so double pole breaking RCDs and main switches are recommended. When sockets are mounted looking downwards then the connector system is rated for outdoor use in all weather. This is also the standard connector for lighting equipment (up to 16 A) used in the British film and television industry (often as outlets from a power splitter with a higher rated 3 phase input).

Dimensions
Connector spec. 16 A 32 A 63 A 125 A
L/N conductor diameter 5 mm 6 mm 8 mm 10 mm
Earth conductor diameter 7 mm 8 mm 10 mm 12 mm
Pin circle diameter 17.5 mm 25.0 mm 36.5 mm 52.5 mm
Outer diameter of shroud 43.5 mm 57.3 mm 69.5 mm 81.6 mm

The shroud diameter does not include the 3 or 4 mm radius keyway protrusion.

Yellow P+N+E, 4h

The yellow P+N+E, 4h (120°) plug is a single phase connector that is in widespread use on the British Isles for 110 V building site and fairground applications. A popular model of this socket type is marketed under the brand name MK Commando which leads to all IEC 60309 sockets to be (incorrectly) referred to as Commando sockets in some descriptions.

Blue 3P+N+E, 9h

16 A 240 V 3P+E+N 9h plug and socket

The blue 3P+N+E, 9h (270°) plug is a three phase connector available in areas with both 110 V and 240 V supply systems (mains). It is prevalent in the outdoor event lighting and audio power industry as an outdoor-safe replacement for NEMA-connectors. In the United States it is not usually used for three phase power but for the high leg delta wiring of split-phase electric power (unknown in Europe). This allows one to choose single-phase AC power at either 110–120 volts between phase and neutral or 220–240 volts between phase and phase. Since these two modes do not need three phases there is also a dark yellow-orange four-pin connector available designed for a single-phase 110–120 or 220–240-volt load.

See also

Wikimedia Commons has media related to IEC 60309.

References

  1. Scope section 1, International Standard 60309-1 edition 4.1 Part 1 General Requirements , 2005, International Electrotechnical Commission, page 13
  2. "Online Assortment of 60309]".
  3. BS EN 60309-1, IEC 60309-1: "Plugs, socket-outlets and couplers for industrial purposes. General requirements." (1999/2012)
  4. BS EN 60309-2, IEC 60309-2: "Plugs, socket-outlets and couplers for industrial purposes. Dimensional interchangeability requirements for pin and contact-tube accessories." (1999/2012)
  5. "General Introduction of CEE plugs and receptacles". Rey & Lenferna. MENNEKES industrial plugs and receptacles. Retrieved 2011-09-03. History: CEE plugs and sockets base on the CEE 17 standard (also BS 4343) which was introduced in the 1960s and that later led to the IEC 60309 standard.
  6. BS EN 60309-4: "Plugs, socket-outlets and couplers for industrial purposes. Switched socket-outlets and connectors with or without interlock." (2007/2012)
This article is issued from Wikipedia - version of the 12/2/2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.